Home> Products> Temperature Transmitter> AQZ Rail Type Temperature Transmitter> AQZ Rail type Temperature transmitter
AQZ Rail type Temperature transmitter
AQZ Rail type Temperature transmitter
AQZ Rail type Temperature transmitter

AQZ Rail type Temperature transmitter

Get Latest Price
Payment Type:T/T,Paypal
Incoterm:FOB,CFR,CIF,EXW
Min. Order:2 Piece/Pieces
Transportation:Ocean,Land,Air,Express
Port:NINGBO,SHANGHAI
Product Attributes

Model No.AQZ

BrandCJ

Packaging & Delivery
Selling Units : Piece/Pieces
Product Description

.General introduction

First of all thank you for using our meter, This manual contains instructions for the installation of meters, operations, parameter setting in the PC. 

AQZ Rail Type Temperature Transmitter is a new type of meter that our Company recently developed, using photoelectric isolation technology, SMT manufacturing process and international standards Din Rail Installation, and have a wide voltage, small size, long life, easy-to-install, and strong anti-interference, and other advantages. Instrumentation is for a group of signal input, two groups simultaneous signal output, communication using ModBus agreement, through RS-485 interface with the PC or PLC-controlled part on-line to concentrate on monitoring and control meters, in connection with the PC Meter can amend the parameters through PC.

. Technical Index

1、Input type: CU50、PT100、K、E、J、T、S、R、WR25、N、F2、0-5V、1-5V

2、Output precision : ±0.5%F.S 

3、Output signal: two group 4~20mA(adjustable through parameter OUTH、OUTL)

4、Overall dimension(mm):106×76×25

5、Power supply:AC/DC 24~36V   

6、Working circumstance:temperature 0~50℃,humidity﹤85%RH without.

corrode and strong electromagnetism disturb.

. Size appearance and meter connection schemeconsult

0

. Code setting mode

Series    code   Name             Remark Setting range Ex-Factory
1  Pb Sensor erroramendment The sensor have deviation can use itemto revisal 0±20.0   0.0
2 FILT Filt modulus The first order lag filter coefficient, the value is greater, the performance anti-jamming moment is stronger, but the response time lag. The pressure and flow control of its value should be smaller, temperature and level control should be relatively large 050 20
3 OUTH Allow exportsmax value Restrain maximum value of adjust output. outL2200 2000
4 OUTL Allow exports  min value Restrain minimum value of adjust output 0outH 400
5 LocK Code lock 0-all the parameter can be revised1-only the SP can be revised 050 0
 

6

 

Sn

 

Input type

‘0’Cu50 –50.0150.0℃‘1’Pt100 –199.9200.0℃‘2’Pt100 –199.9600.0℃;  ‘3’K  -30.01300℃‘4’E  -30.0700.0℃ ;   ‘5’ J  -30.0900.0℃

‘6’T  -199.9400.0℃;    ‘7’ S  -301600℃

‘8’  R  -30.01700.0℃;    ‘9’  WR25 -30.02300.0℃;     

‘10’  N -30.01200.0℃;      ‘11’  Idiosyncratic type

‘12’ 05V(010mA);       ‘13’ 15V(420mA)  

 

013

 

random

7  P-SH Display the high limit P-SH decide the display range, the value and unit are  decided  by  factory and client freely. P-SL9999 random
8 P-SL Display the low limit P-SL decide the display range, the value and unit are decided  by  factory and client freely. -1999P-SH random
9 Addr Communication addres The meter’s number in the control system 063 0
10 BAud Communication baud rate ‘0’1200‘1’2400‘2’4800‘3’9600 03 9600

When the meter connect the PC hrough the RS-485, it can amend meter parameters through the PC, parameters order please refer to Table 4-1. The default address for its communications “0″, the baud rate for “9600″. To connect multiple meters, the PC software address amend for “0″, baud rate changed to “9600″, at this time connecting on a meter, the menu address parameters will be changed to other numerical parameters (not larger than 63), after editing and then another meter to amend the address. Each meter is the only address, can not be repeated. And so on until the end of amending the connecting instrument..Meter communications and parameters amending

Note: When the meter amended the address, the address numerical value labeled best on the meter avoiding confusion. PC software use refers to the help function in PC software.  

4~20mA or 0~10mA linearity current input can achieve by changing 250Ω or 500Ωresistance to 1~5V or 0~5V voltage signal,and then input from A2、28 terminal.

. Fault Analysis and Clearance

Safety fence adopt advanced production process, and have the strict test before leaving factory, it improve the reliability of the meter .The usual fault caused by the wrong operation or parameter setting .If you find the fault couldn’t be cope with, please record it,and contact with the agent or us. Sheet 6-1 is the usual fault of Safety fence in the daily application:

Sheet 6-1 Common fault handling

fault symptom analysis of causes Disposal  measurement
Abnormal power 1Poor contact of power cord

2Power switch without lose

Check the power
PC display do not correlate with the facts.display‘FF’ 1Sensor model mismatch

2Wrong signal connection

1Check sensor model and meter interior input parameter 2check signal wire

3Check communication wire

Abnormal output 1Wrong connecting output wire 1Check output connection

2Check parameter OUTHOUTL


  • Previous: ZW Series Three Phase Multi function Panel Meter
  • Next: 2019 China New Design Bimetal Temperature controller Kts Kto Jto Jts 011 Regulator Enclosure Thermostat

  • Contact

    • Tel: 86-574-58221595
    • Whatsapp: +8618957481197
    • Email: vera@yycj.com
    • Address: No. 9, Changqing Road, Yuyao, Ningbo, Zhejiang, China, Ningbo, Zhejiang China

    Send Inquiry

    Send Inquiry
    *
    *

    We will contact you immediately

    Fill in more information so that we can get in touch with you faster

    Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

    Send