Home> News> XMTD-JK408 four-way intelligent temperature controller
March 02, 2024

XMTD-JK408 four-way intelligent temperature controller

XMTD-JK408 four-way Temperature controller

temperature control meter temperature meter

Instruction manual

Ⅰ.Summary

XMT*JK four-way Temperature Controller can connect four sensors synchronously and conveniently, diminish the instrument`s volume. It has a separate auto-tune mode and PID parameter function with more precision and more reliability in whole machine control.

Ⅱ.Primary technical standard:

1.Input signal: CU50(-50.0~150.0℃).Pt100(-19.9~600.0℃).K(0~1300℃).

E(0~700.0℃).J(0~900.0℃)

2.Accuracy: ±0.5%F.S±byte

3.Output method: relay AC220V 3A(resistance load)

4.control mode: difference control-on/off and PID control

5.Input power: AC110~242V 50/60Hz

6.Environment Temperature: 0 to 50, Humidity: 85%RH

7.Face Size: 160×80×110 mm Hole Size : 152×76 mm

96×96×110 mm Hole Size : 92×92 mm

72×72×110 mm Hole Size :68×68 mm

Ⅲ.Panel board instruction

Ⅳ.connection scheme

connection indicator :

PS:1.MiNi printer connection

Printer down-lead no

Meter port

21

R

19

T

10-18

GND

others

None

2.RS485 communication:connect corresponding `VA+,VB-`.

3.RS232 communication:connect corresponding `R`.`T`.`GND`.

4.only one function can be used between printer and communication functions at one time.

Ⅴ.Code setting mode

Series

Code

Name

Setting range

Manual

Remarks

first

0

LOCK

Code lock

0~50

18-all the parameter can be revised,

18

1

Sn

Input type

0~4

CU50.Pt100.K.E.J

K

2*

ALP

Alarm define

0~6

0:no alarm.1:upper limit alarm.2:low limit alarm.3:upper warp alarm.4:low warp alarm.5:between besides alarm.6:between inside alarm

1

3

t

Output cycle

0~120 S

relay control action cycle setting

10 S

4

dp

display accuracy

0~1

0. no decimal; 1.have decimal

0

5

P-SH

Upper limit

P-SL~full range

this parameter resreict enactment

value`s upper

according request

6

P-SL

lower limit

Range jumping-off ~P-SH

this parameter resreict enactment

value`s low

according request

7

OPB

Assistant output method

0~2

0. no Assistant output;

1.RS485 communication

2.Mini pinter

0

8

Add

address

1~64

(1~9999)

Meter`s NO

(in minitype as print times)

1

9

bt

baud rate

0~3

0:1200; 1:2400;

3:4800; 4:9600

9600

Second

10

SP+N(1~4)

N channels control setting

Range by P-SL.P-SH decide

Control value setting

default

11

AL+N

Alarm value setting

Range by P-SL.P-SH decide

Output mode decide by `AL-P`

default

12

SC+N

Sensor error amendment

±20.0

The sensor have deviation can use item to revisal

0

13

P+N

Proportion modulus

0~100

When the P increase,the the proportion function decrease

When P=0,the meter

is ON/OFF control

8

14

I+N

Calculus time

0~3000

It`s mainly used to adjust

the static difference. To

increase it, the static

difference will be reduced

, but when it is too high,

the static difference will

drift instability.

240

15

d+N

differential time

0~200S

When the I,the calculus function;

Ithe calculus function.

When I=0, no calculus function, it is PD adjustment instrument

30

16

Hy+N

Main control by

drop in level

0.1~50.0

-

1.0

17*

At+N

Setting itself

0~1

0:close setting itself

function 1:open setting

inself function

0

Ⅵ.Technical indexes

1. Accurately connect uires according as connect indicator,power on.

2. Press `SET key` for 3 seconds,enter into first menu.then `parameter `and paraneter value tims will be shown respectively about `CH1 window` and `CH2 window`,you can adjust these parameters by poressing `▲`.`▼`.`◄`.and save the setting by prwss `SET key `,every parameter should be saved after setting ,then enter next parameter set.

3. You can press `CH1`.`CH2`.`CH3`.`CH4` for 3 seconds to enter into corrseponding channel menu .After finished one parameter set,press `SET` to save it,then enter into next parameter set .

Ⅶ.Setting itself

The meter use in the first time or the surroundings have changer, finding it control not good, in this time you need use the setting itself. For example:The first set the AT=1,A-M light flickered, the meter enter into setting itself, press the SET key enter into parameter setting. Set the Hy is 0.5~1, if the output is relay set the t=2S, the meter have three times vibrate, automatic preserved P, I, D parameter and the A-M light off, the setting itself finish.

.Fault Analysis and Clearance

XMT*JK408 adopt advanced production process, and have the strict test before leaving factory, it improve the reliability of the meter .The usual fault caused by the wrong operation or parameter setting .If you find the fault couldn`t be cope with, please record it, and contact with the agent or us. Sheet 8-1 is the usual fault of XMT*JK408 in the daily application:

Sheet 8-1 Common fault disposal

Fault symptom

Analysis of causes

Disposal measurement

Abnormal power

1.poor contact of power cord

2.power switch without lose

Check the power

Signal display do not correlate with the facts.(display `HH`or `L`)

1.Sensor model mismatch

2.wrong signal connect ion

1.check sensor model and meter interior input parameter

2.check signal wire

Abnormal control output

wrong connection of output wire

Check output connection

★Remark:Our company will improve product technology, design and specification, it is confirm to the object.

Attached 1:Statement of meter`s parameter attention letter and English letter

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

Share to:

LET'S GET IN TOUCH

Contact

  • Tel: 86-574-58221595
  • Whatsapp: +8618957481197
  • Email: vera@yycj.com
  • Address: No. 9, Changqing Road, Yuyao, Ningbo, Zhejiang, China, Ningbo, Zhejiang China

Send Inquiry

We will contact you immediately

Fill in more information so that we can get in touch with you faster

Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

Send