Ⅰ.Summary
XMT*JK four-way Temperature Controller can connect four sensors synchronously and conveniently, diminish the instrument`s volume. It has a separate auto-tune mode and PID parameter function with more precision and more reliability in whole machine control.
Ⅱ.Primary technical standard:
1.Input signal: CU50(-50.0~150.0℃).Pt100(-19.9~600.0℃).K(0~1300℃).
E(0~700.0℃).J(0~900.0℃)
2.Accuracy: ±0.5%F.S±byte
3.Output method: relay AC220V 3A(resistance load)
4.control mode: difference control-on/off and PID control
5.Input power: AC110~242V 50/60Hz
6.Environment Temperature: 0 to 50℃, Humidity: ≤85%RH
7.Face Size: 160×80×110 mm Hole Size : 152×76 mm
96×96×110 mm Hole Size : 92×92 mm
72×72×110 mm Hole Size :68×68 mm
Ⅲ.Panel board instruction
Ⅳ.connection scheme
connection indicator :
PS:1.MiNi printer connection
Printer down-lead no | Meter port |
21 | R |
19 | T |
10-18 | GND |
others | None |
2.RS485 communication:connect corresponding `VA+,VB-`.
3.RS232 communication:connect corresponding `R`.`T`.`GND`.
4.only one function can be used between printer and communication functions at one time.
Ⅴ.Code setting mode
Series | Code | Name | Setting range | Manual | Remarks | ||||
first | 0 | LOCK | Code lock | 0~50 | 18-all the parameter can be revised,
| 18 | |||
1 | Sn | Input type | 0~4 | CU50.Pt100.K.E.J | K | ||||
2* | ALP | Alarm define | 0~6 | 0:no alarm.1:upper limit alarm.2:low limit alarm.3:upper warp alarm.4:low warp alarm.5:between besides alarm.6:between inside alarm | 1 | ||||
3 | t | Output cycle | 0~120 S | relay control action cycle setting | 10 S | ||||
4 | dp | display accuracy | 0~1 | 0. no decimal; 1.have decimal | 0 | ||||
5 | P-SH | Upper limit | P-SL~full range | this parameter resreict enactment value`s upper | according request | ||||
6 | P-SL | lower limit | Range jumping-off ~P-SH | this parameter resreict enactment value`s low | according request | ||||
7 | OPB | Assistant output method | 0~2 | 0. no Assistant output; 1.RS485 communication 2.Mini pinter | 0 | ||||
8 | Add | address | 1~64 (1~9999) | Meter`s NO (in minitype as print times) | 1 | ||||
9 | bt | baud rate | 0~3 | 0:1200; 1:2400; 3:4800; 4:9600 | 9600 | ||||
| |||||||||
Second | 10 | SP+N(1~4) | N channels control setting | Range by P-SL.P-SH decide | Control value setting | default
| |||
11 | AL+N | Alarm value setting | Range by P-SL.P-SH decide | Output mode decide by `AL-P` | default | ||||
12 | SC+N | Sensor error amendment | ±20.0 | The sensor have deviation can use item to revisal | 0 | ||||
13 | P+N | Proportion modulus | 0~100 | When the P increase,the the proportion function decrease When P=0,the meter is ON/OFF control | 8 | ||||
14 |
I+N |
Calculus time |
0~3000 | It`s mainly used to adjust the static difference. To increase it, the static difference will be reduced , but when it is too high, the static difference will drift instability. | 240 | ||||
15 | d+N | differential time | 0~200S | When the I↓,the calculus function↑; I↑the calculus function↓. When I=0, no calculus function, it is PD adjustment instrument | 30 | ||||
16 | Hy+N | Main control by drop in level | 0.1~50.0 | - | 1.0 | ||||
17* | At+N | Setting itself | 0~1 | 0:close setting itself function 1:open setting inself function | 0 |
Ⅵ.Technical indexes
1. Accurately connect uires according as connect indicator,power on.
2. Press `SET key` for 3 seconds,enter into first menu.then `parameter `and paraneter value tims will be shown respectively about `CH1 window` and `CH2 window`,you can adjust these parameters by poressing `▲`.`▼`.`◄`.and save the setting by prwss `SET key `,every parameter should be saved after setting ,then enter next parameter set.
3. You can press `CH1`.`CH2`.`CH3`.`CH4` for 3 seconds to enter into corrseponding channel menu .After finished one parameter set,press `SET` to save it,then enter into next parameter set .
Ⅶ.Setting itself
The meter use in the first time or the surroundings have changer, finding it control not good, in this time you need use the setting itself. For example:The first set the AT=1,A-M light flickered, the meter enter into setting itself, press the SET key enter into parameter setting. Set the Hy is 0.5~1℃, if the output is relay set the t=2S, the meter have three times vibrate, automatic preserved P, I, D parameter and the A-M light off, the setting itself finish.
Ⅷ.Fault Analysis and Clearance
XMT*JK408 adopt advanced production process, and have the strict test before leaving factory, it improve the reliability of the meter .The usual fault caused by the wrong operation or parameter setting .If you find the fault couldn`t be cope with, please record it, and contact with the agent or us. Sheet 8-1 is the usual fault of XMT*JK408 in the daily application:
Sheet 8-1 Common fault disposal
Fault symptom | Analysis of causes | Disposal measurement |
Abnormal power | 1.poor contact of power cord 2.power switch without lose | Check the power |
Signal display do not correlate with the facts.(display `HH`or `L`) | 1.Sensor model mismatch 2.wrong signal connect ion | 1.check sensor model and meter interior input parameter 2.check signal wire |
Abnormal control output | wrong connection of output wire | Check output connection |
★Remark:Our company will improve product technology, design and specification, it is confirm to the object.
Attached 1:Statement of meter`s parameter attention letter and English letter
A | B | C | D | E | F | G | H | I | J | K | L | M |
|
|
|
|
|
|
|
|
|
|
|
|
|
N | O | P | Q | R | S | T |
LET'S GET IN TOUCH
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.
Fill in more information so that we can get in touch with you faster
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.