XMTL-908 series intellective Temperature controller

XMTL-908 series intellective temperature control meter

XMT*908 series intelligence Temperature controller uses nowadays the advanced monolithic microcomputer as mainframe,reduce peripheral assembly,and improve the reliability;It adopts the control method of vague theory combined with traditional PID control, and make the control process with the advantage of rapid response.small overshoot.high steady state precision. It is intelligence Temperature Controller with the function of high performance.high reliability.complete input,its function is suitable to all the occasion needed temperature measurement and control,also be compatible with other industrial parameter measurement and control.

Main technical specification

l Measurement deviation: ≤±0.5%F·S±1

l Cold end compensating deviation: ≤±2.0℃

l Sampling cycle: 0.5S

l Control cycle: relay output 2~120S , other is 2S.

l Relay output contact capacity: AC250V/7A (resistance load) or AC250V/0.3A (perceptual load)

l Driving controllable pulse output: ≥3V scope, ≥40us width`s over zero or trigger contact pulse

l Driving solid relay signal output: driving electric current≥15mA, voltage≥9V.

l Continuous PID : 0~10mA (load 500±200Ω), 4~20mA (load 250±100Ω),

or 0~5V (load≥100kΩ) , 1~5V (load≥100kΩ)

l Power supply: AC85V~242V, 50/60Hz

l Working condition: temperature 0~50.0℃, relative humidity≤85%RH, without corrode and strong electric radiation.

Ⅱ.Product code:

XMT 9 8

(1) ⑵ (3) (4)(5)

(1) Meter faceplate dimension

Blank: 160mm × 80mm x 120mm Installation hole: 152mm x 76mm

A: 96mm x 96mm x 110mm Installation hole: 92mm x 92mm

D: 72mm x 72mm x 110mm Installation hole: 68mm x 68mm

E: 48mm x 96mm x 110mm Installation hole: 44mm x 92mm

F: 96mm x 48mm x 110mm Installation hole: 92mm x 44mm

S: 80mm x 160mm x 120mm Installation hole: 76mm x 156mm

G: 48mm x 48mm x 110mm Installation hole: 44mm x 44mm

(2)Design serial number

(3)Alarm

[ 0": no alarm [ 1or2": one alarm (upper limit, lower limit) [5": voice alarm

[ 3": two group alarm (upper limit, lower limit, positive deviation alarm and negative deviation alarm discretionary setting)

(4)Input signal

[8": Free exchange of the input signal

⑸Control method

Blank: Relay contact

[ A": Single-phase over-zero trigger adjustment

[ A3": Three-phase over-zero trigger adjustment

[ B": Single-phase shift-phase trigger adjustment

[ B3": Three-phase shift-phase trigger adjustment

[ C": 0-10mA or 4-20mA constant electric current output

[ G": Solid state relay (SSR) output

Ⅲ.panel instruction(consult)

Ⅳ.Code setting mode

Series

Code

Name

Setting range

Manual

Remarks

0

SP

Appointed data

Determined by P-SL P-SH

-

50.0

1

AL-1

Alarm 1

Determined by P-SL,P-SH when the upper and lower limit range,it is0~50.0 when the upper and lower limit deviation alarm

Alarm 1 setting value

10

2

AL-2

Alarm 2

Determined by P-SL,P-SH when the upper and lower limit range,it is0~50.0 when the upper and lower limit deviation alarm

Alarm 1 setting value

10

3

P

Proportion modulus

0~100

When the P,the the proportion function

When P=0,the meter is ON/OFF control

8

4

I

Calculus time

0~2000S

240

5

d

differential time

0~200S

30

6

At

Setting itself

ON:open setting inself function

OFF:close setting itself function

Select of setting itself

OFF

7

t

SSR proportion Control period

1~120S

the movements cycle ON/OFF of Setting relays control is no meaning

20

8

Hy

Main control by

drop in level

0.1~50.0

Only have meaning when main control output is ON/OFF(P=0)

1.0

9

Hy-1

Alarm 1

drop in level

0.1~50.0

It has use drop in level setting of alarm contact output

1.0

10

Hy-2

Alarm 2

drop in level

0.1~50.0

It has use dropin level setting of alarm contact output

1.0

11

Pb

Sensor error amendment

±20.0

The sensor have deviation can use item to revisal

0

12

FILT

Filt modulus

0~50

Is the software filter constants of measurement sampling.The constant ,the Measurements antijamming capabilityMeasurements antijamming capability,but the measurement and system time

20

13

dp

Show accuracy

0~1

0: have radix point,1: have no radix point

-

14

P-SH

Display the high limit

P-SL~9999

Can set the high limit displaying input signal

400

15

P-SL

Display the low limit

-1999~P-SH

Can set the low limit displaying input signal

0

16

OUTL

Allow exports min value

0~OUTH

It will no role when highest outputlimit,,manual and position.

200.0

17

OUTH

Allow exports max value

OUTL~200

It will no role when lowest outputlimit,,manual and position.

0.0

18

ALP1

Alarm1 and output definition

0~4

`0`:indicate no alarm

`1`:upper limit touch alarm

`2`:lower limit touch alarm

`3`:upper windage alarm

`4`:lower windage alarm

-

19

ALP2

Alarm2 and output definition

0~4

-

20

COOL

System function choice

0~1

`0`:reverse control

`1`:positive control

0

21

OPPO

Open power output

0~100

Soft start functionthat meters coefficient after first export of electric power

0

22

LOCK

Code lock

0~50

0- all the parameter can be revised

1- only the sp can be revised

0

23

Sn

Input type

0~70.

0-CU50 (-50.0~150.0) ;1-PT1 (-200.0~200.0) ;2-PT2 (-200.0~600.0) ;3-K (0~1300) ;4-E (0~700.0) ;5-J (0~900.0) ;6-T (-200~400.0) ;7-S (0~1600) ;

24

OP-A

Output type

1~4

1- RLP SSR output mode

2- SSR solid state relay

3- Zero controllable silicon contact signal when it exceed zero output mode

4- Mut controllable silicon phase trigger contact output mode

5- 0~10MA linearity control electric current output

6- 4~20MA linearity control electric current output

Ⅴ.Technical indexes

1. The first setting area

Press the SET key 3S enter into the first setting area, the meter will display the parameter code 1~24in the window at the upper row and display the parameter data at the low row. In this time press the ▲.▼ or t key to adjust the parameter, then press the SET key to preserve. Press the SET key long time will withdraw or press the SET+ƒ key will directly withdraw. If within 10 seconds do not press every key then it will automatically to preserve the data and withdraw the setting.

2. The second setting area

When the meter is set up with the electricity, press the SET key enter into the second setting area, you can according the 1 to set the [SP".

3. Manual regulation

When the meter is set up with the electricity, press the t key about 3S enter into the manual regulation, it will display [H" at the lower row, in this time can set the output power; press the t key about 3S again it will withdraw the manual regulation.

Ⅵ.Setting itself

The meter use in the first time or the surroundings have changer, finding it control not good, in this time you need use the setting itself. For example:

The first set the AT=ON,A-M light flickered, the meter enter into setting itself, press the SET key enter into parameter setting. Set the Hy is 0.5~1, if the output is relay set the t=2S, the meter have three times vibrate, automatic preserved P, I, D parameter and the AT light off, the setting itself finish.

Ⅶ.connection scheme(consult)

Share to:

LET'S GET IN TOUCH

Contact

  • Tel: 86-574-58221595
  • Whatsapp: +8618957481197
  • Email: vera@yycj.com
  • Address: No. 9, Changqing Road, Yuyao, Ningbo, Zhejiang, China, Ningbo, Zhejiang China

Send Inquiry

We will contact you immediately

Fill in more information so that we can get in touch with you faster

Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

Send