XMTA-608 Series intellgence digital temperature control instrument

.Summarize

XMT*-608 series Intelligent Temperature Controller,is double row 3-LED display, respectively display temperature measurement value (PV) and setting value (SV). The controller can input kinds of signals which are used interchangeably, three-button operation, adopts ON/OFF control and PID control .It allows an easy parameter setting and convenient inputting, is used widely temperature automatic control systems of machinery.chemical.ceramics.light industrial.metallurgy.petrifaction and heat treatment and so on.

.Main Technical Indexs

1.Measurement deviation:±0.5%F·S±1B,Cold end compensating deviation≤±2℃

2.Input(can be selected):CU50(-50~150).PT100(-199~600).K(-30~999).

E(-30~700).J(-30~900).T(199~400)

3.Relay output contact capacity:AC220V 5A(resistance load)

period 2~120s can be adjusted.

4.Drivng solid relay signal output:driving electric current >15m A voltage >9V,

period is 2S

5.Power:AC85V~242V,50/60HZ

6.Work environment:temperature 0~50.0℃, relative humidity≤85%RH, without corrode and strong electric radiation.

.Instrument panel and connection scheme

1.Instrument panel(consult)

2.Connection scheme(consult)



.Code setting sheet

Series

Code

Name

Setting range

Remark

Ex-Factory

First

Menu

0

-

Appointed data

Determined

by

and

Press▲or▼for 3 second and set the temperature setting value you need

-

1

High/Low-limit

alarm

Determined

by

and

-

Random

2

Measurement

deviation

-20.0~20.0

Measuring value can be modified through increasing or decreasing this data.

0

3

Proportion time

0~99.9~200

When the P↑,the proportion and differential

function↓;If the P↓,the proportion and

differential function↑

When P=0,the meter is ON/OFF control.

15.0

4

Calculus time

0~999

It`s used to adjust static difference. To increse it,the static difference will be reduced, but if it is too high, the static difference will drift instability.

240

5

Differential time

0~200

30

6

Control period

2~120S

When it leaves factory, SSR is 2s;

Relay is 20s.

When P=0, it makes no sense.

20

7

Main control by drop in level

0.1~50.0

It only controls at ON/OFF

1.0

8

Parameter setting itself

/

-shut itself function ;

-open itself function

Select ``only can adjust for one time,and then turn back to ``

9

Electronics

lock

0~50

=0 all the parameter can be revised

=1 only the appointed data can be revised

0

Second

Menu

10

Electronics

lock

0~50

idem

0

11

Input type

-

CU50().PT100().K().E().J().T();

K

12

Set lower limit

CU50(-50~150).

PT100(-80~600).

K(-30~999).E(-30~700).

J(-30~900).T(199~400)

0

13

Set upper limit

400

14

Filt modulus

0~50

It is the software filter constant of measurement sampling.The constant ↑,the measurement antijamming capability↑,but the measurement speed and system response time ↓

20

15

System function

choice

/

:positive control(cooling control)

:reverse control(heating control)

.Flow chart

.Operation

1. Electrify after taking into the power, Sensor and control circuit according to the connection scheme,and then the instrument start testing itself for 1 second.

2. After testing itself, the instrument enters into normal condition,the upper row window displays tested value, underside row window(SV) displays the setting value.

3. Modify the setting value

Press or key for 3S, the upper row window displays tested value,underside row window(SV) display the setting value. Press or key to modify,for long time press the key can accelerate. After modification, press SET to save and exit .If you don`t do this operation, it can be done itself.

4. Interior Technical Indexes setting(Technical Indexes refer to the sheet)

(1) The first menu(1~9)

Press SET key 3S to enter into the first menu, the upper window displays Indexe symbol, underside window diplays Index value. Press or key to modify,for long time press the key can accelerate. After modification, press SET to save and enter into the next Indexs setting. if you don`t do this operation,it can be done itself.

(2)The second menu(10~15)

Press SET and key 3S enter into the second menu, and the setting method is the same as the first menu.

5. Set itself

The meter is used in the first time or the surroundings have changer, finding it control not good, this time you need use the setting itself. For example:

First set the fixed value, and then enter the menu , set is 0.5~1.0,set to ,and the At light is light,the controller enters into setting itself state, here the controller is ON/OFF control,after three times oscillation,new parameter .. can be confirmed and saved,AT light goes out,the controller be reset and enters into the control state.

XMT*-608 series intelligent Temperature controller,the controller is double row 3-LED display, respectively display temperature measurement value (PV) and setting value (SV). The temperature control instrument can input kinds of signals which are used interchangeably, three-button operation, adopts ON/OFF control and PID control .It allows an easy parameter setting and convenient inputting, is used widely temperature automatic control systems of machinery.chemical.ceramics.light industrial.metallurgy.petrifaction and heat treatment and so on.

.Model sense

XMT□-6 8

1 2 3 4 5

1:External size and Installation hole(mm):

Empty: 160×80×90 152×76 A: 96×96×90 92×92

D: 72×72×90 68×68 E: 48×96×90 44×92

F: 96×48×90 92×44 G: 48×48×100 44×44

S: 80×160×90 76×152 B:60×120×90 56×116

C:80×120×35 wall set installation

2: Operation display method:`6`: 3-key gentel push-switch setting, double row digital display, have PID adjustment

3: An additional alarm:

Blank or `0`: indicates no alarm;`1`: High limit touch alarm;`2`: low limit touch alarm

4:Input signal classification: `8`:input signal can interchange free

5: Suffix: None:relay output G:solid state relay output

.Fault analysis and clearance

XMT*-608 adopts advanced production process, and has the strict test before leaving factory, it improve the reliability of the meter .The usual fault is caused by the wrong operation or parameter setting .If you find the fault couldn`t be cope with, please record it,and contact with the agent or us. Sheet 8-1 is the usual fault of XMT*-608 in the daily application:

Share to:

LET'S GET IN TOUCH

Contact

  • Tel: 86-574-58221595
  • Whatsapp: +8618957481197
  • Email: vera@yycj.com
  • Address: No. 9, Changqing Road, Yuyao, Ningbo, Zhejiang, China, Ningbo, Zhejiang China

Send Inquiry

We will contact you immediately

Fill in more information so that we can get in touch with you faster

Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

Send