Home> News> XMT-JK808 series 8 channel intellective temperature controller
March 23, 2024

XMT-JK808 series 8 channel intellective temperature controller

XMT-JK808 series 8 channel intellective Temperature controller

XMT-JK808 series Intelligent Temperature Controller is a new meter to meet the market needs. The meter is controlled by single chip microcomputer, every channel setting value and some parameters can be set up independently. It has the advantages of small volume, low power consumption, simple operation, easy control, stable operation, reliable, economical characteristics. It is widely used in the temperature automatic control systems of machinery.chemical.ceramics.light industrial.metallurgy.petrifaction and heat treatment, and so on.Temperature Sensor

.Main technical specification

1.Input(can be selected):CU50(-50~150).PT100(-80~600).K(-30~999).

E(-30~700).J(-30~900).T(199~400)

2.Measurement deviation: ≤±0.5%F·S±1B Cold end compensating deviation: ≤±2.0℃

3.Sampling cycle: 0.5S

4.Control cycle: relay output 2~120S , other is 2S.

5.Relay output contact capacity: AC220V/5A (resistance load) or AC220V/0.3A (perceptual load)

6.Alarm relay contact output:AC220V/1A(resistance load)

7.Driving solid relay signal output: driving electric current≥15mA, voltage≥9V.

8.Power supply: AC85V~242V, 50/60Hz

9.Working condition: temperature 0~50.0℃, relative humidity≤85%RH, without corrode and strong electric radiation.

.Panel instruction(consult)

ALM1~ALM8:The first channel to the eighth channel alarm output indicator light ( red);

OUT1~OUT8:The first channel to the eighth channel control output indicator light ( green );

CH1~CH8 key:The first channel to the eighth channel corresponding channel parameter setting key;

SET/key:The first channel to the fourth channel function setting key;

SET/key:The fifth channel to the eighth channel function setting key;

key(left):The first channel to the fourth channel shift key;

key(right):The fifth channel to the eighth channel shift key;

key(left):The first channel to the fourth channel data decrease key;

key(right):The fifth channel to the eighth channel data decrease key;

key(left):The first channel to the fourth channel data increase key;

key(right):The fifth channel to the eighth channel data increase key;

.Model significance:

XMT - JK 8 8

(1) (2) (3) (4) (5) (6)

Meter faceplate and Installation dimension(mm):160×80×130; 152×76;

Design serial number:Eight channel independent control meter, PID and ON/OFF control can optional;

Alarm:`0`:no set alarm; `1`:one alarm ( alarm mode optional);

Input signal: [8": Free exchange of the input signal

Main control mode: `space`: relay normally-open normally-closed contact output;

`A`:Single phase zero trigger control; `G`:Solid state relay control output

(6) Suffix:`K`:with 485 or RS232 Communication module interface;

`WT`:With an external printer module interface

.Internal parameters:

Series

Code

Name

Setting range

Manual

Ex-Factory

First

Menu

0

LOCK

Electronics

lock

0~50

LOCK=18 all the parameter can be revised;

LOCK≠18 all the parameter can not be revised

18

1

Sn

Input type

..

..

CU50()-50.0~150.0℃

Pt100()-199.9~600.0℃

K(). -30.0~1300℃

E(). -30.0~700.0℃

J() -30.0~900.0℃

2

ALP

Alarm output definition

0~6

`0`no alarm; `1`upper limit alarm;

`2`lower limit alarm;

`3`positive deviation alarm

`4`negative deviation alarm.

`5`outside the interval alarm

`6`inside the interval alarm

1

3

t


Share to:

LET'S GET IN TOUCH

Contact

  • Tel: 86-574-58221595
  • Whatsapp: +8618957481197
  • Email: vera@yycj.com
  • Address: No. 9, Changqing Road, Yuyao, Ningbo, Zhejiang, China, Ningbo, Zhejiang China

Send Inquiry

We will contact you immediately

Fill in more information so that we can get in touch with you faster

Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

Send