Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.
XMT-JK1201 12 channel Digital Temperature Controller
The XMT-JK1201 series digital Temperature controller can connection 12 road Sensor and control 12 road temperature at one time. It is advantage for connection at scene.
Ⅰ. Main technical standard
1) Input: Thermocouple: K .J
2) Display precision: superior to 0.5 degree
3) Control method: ON/OFF drop in level control, PID control
4) Output method: 5A relay , solid state relay and silicon controlled over zero spring output
5) Working power: AC220V 50Hz , the power`s consumption is less than 4W
6) Size(mm): 160x 80 x 125 ; Installation hole(mm): 152x 76
Ⅱ. Face indicator
The face have 8 or 12 displays, difference use show every single road measured value every one time.
It has a radix point right LED every display, the radix point is turning on, this way has control output. the radix point is turning off, this way hasn`t control output.
Ⅲ. Parameter
Series | Attention | Name | Manual | Range | Remark | |
First step menu |
0 |
SP | Appointed value | Press ▲ and ▼ key to set | All range | Random |
Second
step
menu |
1 |
AL |
Alarm | When the measurement value more than setting value have alarm |
All range |
Random |
2 |
SC | Measurement deviation revisal | The measurement value can be added or deduct by this item to revisal |
±20.0 |
0 | |
3 |
P |
Proportion area | Proportion area = P x 20, When the P↑, proportion function↓, clash↓, but too little will add the heating time When P=0, the instrument is ON/OFF control |
0~100 (the user don`t set the P more than 100) |
15.0 | |
4 |
I |
Integral time | Integral time too big will leave something the system , if too little it will have |
0~2000s |
240 | |
5 | d | Differential time | - | 0~200s | 30 | |
6 | t | Control period | - | 2~120s | 10 | |
7 |
Hy | Main control and alarm drop in level |
- |
0~50.0 |
1.0 |
Ⅳ.Setting the parameters
1.Set the first step menu SP: Press the ▲ or ▼ key 3s enter into the first step menu parameter, code and parameter value will alternate display, press the ▲ or ▼ key long time to Decreases or Increases the parameter value, setting finish , then press ▲ and ▼ key will preserve and return out. If within 10 seconds do not press every key then it will automatically preserve and return out.
2.Set the second step menu: Press the ▲ and ▼ key 3S enter into the second step menu, in this time code and parameter value will alternate display, press the ▲ or ▼ key long time to Decreases or Increases the parameter value, when the setting finished, press ▲ and ▼ key will return out and enter into the next parameter. Use the same idea to set other parameter. If within 10 seconds do not press every key then it will automatically preserve and return out.